Heating circuit settings:
Para-
meter
Parameter name Parameter description Setup range Default
value
P2.1
HEATING CURVE STEEP-
NESS
The heating curve steepness informs the user of the
required temperature of heating devices at certain
outdoor temperature. See section “Heating curve".
0.1 ÷ 2.6
0.5–oor
heating
1.0–radia-
tors
P2.2
PARALLEL SHIFT OF
HEATING CURVE
Set up the parallel shift of the heating curve or the
calculated temperatures of the stand-pipe.
The setting can be used to eliminate the deviation
between the requested and actual room temperature.
-15 ÷ 15°C
0
P2.3
DURATION OF BOOST
HEATING
Set up the duration of the increased preferred room
temperature in the transition from night to day heating
interval.
0 ÷ 200min
0
P2.4
ROOM TEMPERATURE
INCREASE BY BOOST
HEATING
Set up the value of the increased requested room
temperature in the transition from night to day heating
interval.
0 ÷ 8°C
3
P2.5
THE PRIORITY OF D. H.
W.WARMING
Set up the priority of sanitary water heating before
heating the heating circuit.
0–NO
1–YES
0
P2.6
COOLING CURVE STEEP-
NESS
The cooling curve steepness provides information
on the required temperature of cooling devices at a
certain outdoor temperature.
0.1 ÷ 2.6
0.5
P2.7
PARALLEL SHIFT OF
COOLING CURVE (°C)
Set up the parallel shift of the cooling curve or the
calculated temperatures of the stand-pipe.
The setting can be used to eliminate the deviation
between the requested and actual room temperature.
-15 ÷ 15°C
0
Settings for boiler or heat source:
Para-
meter
Parameter name Parameter description Setup range Default
value
P3.1
MIN. BOILER TEMPERA-
TURE
Set up the minimum temperature of the boiler or heat
source.
1 ÷ 90°C
35
HEATING CURVE
The heating curve slope provides information about the required temperature of heating
devices at certain outdoor temperature. The value of the slope depends mostly on the type
of the heating system (oor, wall, radiator, convection heating) and the thermal insulation of
the building.
Determining the slope of the heating curve
The slope of the heating curve can be calculated if there is enough data available, other-
wise through experience based on the estimate of the heating system dimensioning and
thermal insulation of the building.
The slope of the heating curve is selected correctly if the room temperature remains intact
even at major changes of the outdoor temperature.
As long as the outdoor temperatures are above +5°C, the room temperature can be regu-
lated with the setup change of the day or night temperature or parallel shift of the heating