23
7. Measuring Range Codes
Select measuring range from the following table.
Changing the code initializes all data related to measuring range.
Input type Code Measuring range (°C) Measuring range (°F)
B

*1
0 ~ 1800 °C 0 ~ 3300 °F
R

0 ~ 1700 °C 0 ~ 3100 °F
S

0 ~ 1700 °C 0 ~ 3100 °F

*2
-199.9 ~
400.0 °C -300 ~ 750 °F

0.0
~ 800.0 °C 0 ~ 1500 °F
K

0 ~ 1200 °C 0 ~ 2200 °F
E

0 ~ 700 °C 0 ~ 1300 °F
J

0 ~ 600 °C 0 ~ 1100 °F
T

*2
-199.9 ~
200.0 °C -300 ~ 400 °F
N

0 ~ 1300 °C 0 ~ 2300 °F
PL *3

0 ~ 1300 °C 0 ~ 2300 °F
WRe5-26 *4

0 ~ 2300 °C 0 ~ 4200 °F
U *5

*2
-199.9 ~
200.0 °C -300 ~ 400 °F
Thermocouple
L *5

0 ~ 600 °C 0 ~ 1100 °F
K

*6
10.0 ~
350.0 K 10.0 ~ 350.0 K
AuFe-Cr

*7
0.0 ~
350.0 K 0.0 ~ 350.0 K
K

*6
10
~ 350 K 10 ~ 350 K
Kelvin
AuFe-Cr

*7
0
~ 350 K 0 ~ 350 K

-100.0 ~ 350.0 °C -150.0 ~ 650.0 °F

-200
~ 600 °C -300 ~ 1100 °F

-100.0
~ 100.0 °C -150.0 ~ 200.0 °F

-
50.0 ~ 50.0 °C - 50.0 ~ 120.0 °F
Pt100

0.0 ~ 200.0 °C 0.0 ~ 400.0 °F

-200
~ 500 °C -300 ~ 1000 °F

-100.0 ~ 100.0 °C -150.0 ~ 200.0 °F

-
50.0 ~ 50.0 °C - 50.0 ~ 120.0 °F

0.0 ~ 200.0 °C 0.0 ~ 400.0 °F
R.T.D
JPt100

-100.0 ~ 350.0 °C -150.0 ~ 650.0 °F
-10 ~ 10mV

0 ~ 10mV

0 ~ 20mV

0 ~ 50mV

10 ~ 50mV

Universal-input
mV
0 ~ 100mV

-1 ~ 1V

0 ~ 1V

0 ~ 2V

0 ~ 5V

1 ~ 5V

Voltage
V
0 ~10V

Initial value: 0.0 ~ 100.0
Input scaling setting range: -1999 ~ 9999
Span: 10 ~ 10,000 count
Decimal point position: None, 1/2/3 digits following
decimal point
Lower limit value is less than higher limit value.
NOTE: For current input, install input terminals of the
specified receiving impedance (250 ) and use code
84 (0 ~ 20 mA) or 85 (4 ~ 20 mA).
Thermocouple: B, R, S, K, E, J, T, N: JIS/IEC
R.T.D. Pt100: JIS/IEC JPt100
*1. Thermocouple B: Accuracy guarantee not applicable to 400°C (752°F) or below.
*2. Thermocouple K, T, U: Accuracy of those readings below -100°C is ±0.7% FS
*3. Thermocouple PLII: Platinel
*4. Thermocouple WRe5-26: A product of Hoskins
*5. Thermocouple U, L: DIN 43710
*6. Thermocouple K (Kelvin) accuracy *7. Thermocouple Metal-chromel (AuFe-Cr) (Kelvin) accuracy
Temperature range Temperature range
10.0 ~ 30.0 K ± (2.0%FS + [CJ error ×
20] K + 1K) 0.0 ~ 30.0 K ± (0.7%FS + [CJ error × 3] K + 1K)
30.0 ~ 70.0 K ± (1.0%FS + [CJ error × 7] K + 1K) 30.0 ~ 70.0 K ± (0.5%FS + [CJ error × 1.5] K + 1K)
70.0 ~ 170.0 K ± (0.7%FS + [CJ error × 3] K + 1K) 70.0 ~ 170.0 K ± (0.3%FS + [CJ error × 1.2] K + 1K)
170.0 ~ 270.0 K ± (0.5%FS + [CJ error × 1.5] K + 1K) 170.0 ~ 280.0 K ± (0.3%FS + [CJ error × 1] K + 1K)
270.0 ~ 350.0 K ± (0.3%FS + [CJ error × 1] K + 1K) 280.0 ~ 350.0 K ± (0.5%FS + [CJ error × 1] K + 1K)
NOTE: Unless otherwise specified, the measuring range will be set as follows when shipped from the factory:
Input Standard/rating Measuring range
Multi input K thermocouple 0.0 ~ 800.0°C
Voltage (V) 0 ~ 10V DC 0.0 ~ 100.0, no unit