EasyManua.ls Logo

Siemens 3TK28 - Technical Data 3 TK2841

Siemens 3TK28
206 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of the individual safety relays
3.7 3TK28 safety relays with solid-state enabling circuits
3TK28 safety relays
122 Manual, 07/2016, NEB926157502000/RS-AB/003
3.7.2.7
Technical data 3TK2841
3TK2841-1B...
3TK2841-2B...
EMC emitted interference
IEC 60947-5-1, IEC 60000-4-3,
IEC 60000-4-5, IEC 60000-4-6
Item designation
• according to DIN 40719 extendable after IEC 204-2
according to IEC 750
KT
• according to DIN EN 61346-2
F
Number of sensor inputs 1-channel or 2-channel
1
Design of the cascading
cascading or in-service switching
Type of the safety-related wiring of the inputs
single-channel and two-channel
Product feature
transverse contact-secure
Yes
Safety Integrity Level (SIL) according to IEC 61508
SIL3
SIL claim limit (for a subsystem) according to EN 62061
3
Safety integrity level (SIL)
for delayed release circuit
according to IEC 61508
—
Performance Level (PL)
• according to ISO 13849-1
e
• for delayed release circuit according to ISO 13849-1
—
Category
• according to EN 954-1
4
• according to ISO 13849-1
4
Safety device type according to IEC 61508-2
Type B
Probability of dangerous failure per hour (PFHD)
with high
demand rate according to EN 62061
1/h 0.00000000005
T1 value
for proof test interval or service life
according to
IEC 61508
a 20
Number of outputs
as contact-less semiconductor switching
element
• for reporting function
– non-delayed
0
– delayed switching
0
• safety-related
– non-delayed
2
– delayed switching
0
Stop category according to DIN EN 60204-1
0
Design of the input
• cascading-input/functional switching
Yes
• feedback input
Yes
• start input
Yes

Table of Contents