Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
78 Manual, 07/2016, NEB926157502000/RS-AB/003
3TK2825-.A...
3TK2825-.B...
Product function
automatic start
Yes
rotation speed monitoring
No
laser scanner monitoring
No
light grid monitoring
No
light barrier monitoring
No
magnetic switch monitoring Normally closed contact-
Normally open contact
No
magnetic switch monitoring Normally closed contact-
Normally closed contact
No
emergency stop function
Yes
protective door monitoring
Yes
standstill monitoring
No
step mat monitoring
Yes
monitored start-up
Yes
Acceptability for application
safety-related circuits
Yes
safety cut-out switch
Yes
magnetically operated switches monitoring
No
EMERGENCY-OFF circuit monitoring
Yes
proximity switches monitoring
No
opto-electronical protection device monitoring
No
position switch monitoring
Yes
tactile sensor monitoring
No
valve monitoring
No
Utilization category
DIN EN / IEC 60947-5-1
Rated operational voltage
U
e
[V]
Rated operational current I
e
[A]
if all enabling circuits are loaded
60 °C 70 °C
AC-15
230
6
4
DC-13
24
6
4
115
0.2
0.2
230
0.1
0.1
Continuous current I
th
6
4

Table of Contents

Related product manuals