Engineering and remote access
3.6 SITOP UPS Manager
SITOP UPS1600 / UPS1100
126 Manual, 04.2017, A5E37775406-8-76
Description of the program arguments "upsshutdown.exe":
upsshutdown.exe -[c][r][s]
c: PC is shut down
s: S command is sent to the UPS. The UPS is shut down without any additional delay.
r: R command is sent to the UPS. After the PC has been shut down (no response to ping),
the UPS shuts down after waiting for time "Additional buffer time after PC shutdown".
Example for runupsshutdown.bat:
@echo off
set var = C:\Users\Public\Documents\SitopUPSManager\commands\shutdown
echo "% var %" cd "% var %"
dir > info.txt
upsshutdown.exe -cr
Behavior for missing buffer readiness
Make the settings under "Software configuration > Not ready for buffering".
The following options are available:
Start the application if buffer mode is not possible.
Start the application when buffer readiness returns
Open the SITOP UPS Manager if buffer mode is not possible
Open the SITOP UPS Manager when buffer readiness returns.