Environmental conditions
SITOP UPS1600 / UPS1100
226 Manual, 04.2017, A5E37775406-8-76
Table 10- 2 UPS1100
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
6EP4135-0GB00-0AY0
(12 Ah)
6EP4132-0GB00-0AY0
(2.5 Ah)
6EP4133-0JB00-0AY0
(5 Ah)
Ambient temperature 0 ... 40 °C for natural con-
vection (self convection)
1.2 / 3.2 / 7 Ah:
From product version 3:
-15 ... 50 °C for natural con-
vection (self convection)
12 Ah:
From product version 2:
-15 ... 50 °C for natural con-
vection (self convection)
-20 ... 60 °C for natural con-
vection (self convection)
-20 ... 50 °C for natural con-
vection (self convection)
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Remark: The service life of the UPS1100 battery modules
(decrease to 50 % of the original capacity) depends on the
battery temperature, at approximately 20 °C: 4 years, 30 °C:
2 years, 40 °C: 1 year
Transport and storage tem-
perature
-20 ... 50 °C
-40 ... 60 °C
-40 ... 60 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class Climatic class 3K3 according to EN 60721, 5 - 95 % no
condensation
Degree of pollution
2
Mechanical stressing in
operation
Tested according to:
EN 60068-2-6 Vibration, test Fc:
3.5 mm deflection in the range 59 Hz
1 g acceleration in the range 9150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms