EasyManua.ls Logo

Siemens 6EP4135-0GB00-0AY0

Siemens 6EP4135-0GB00-0AY0
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Environmental conditions
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
227
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
6EP4135-0GB00-0AY0
(12 Ah)
6EP4132-0GB00-0AY0
(2.5 Ah)
6EP4133-0JB00-0AY0
(5 Ah)
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Air pressure Operation:
1080 - 795 hPa (-1000 - 2000 m)
Operation at altitudes of 4000 m above sea level and
higher is not permissible (exception, 2.5 Ah).
Operation at installation altitudes of 2000 - 6000 m
above sea level:
output power derating of -7.5 % / 1000 m - or
reduction of the ambient temperature by 5 K / 1000 m
see Figure 6-20 Altitude derating (Page 202)
Storage:
1080 - 660 hPa (-1000 - 3500 m)

Table of Contents

Related product manuals