Engineering and remote access
3.5 Cyclic and acyclic data
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
99
Data
Description
Data type
Start from battery Start from battery: Setting at the signal terminal for function "Start
from battery".
Unsigned8
Selected battery profile Profile of the selected battery: The battery charging behavior is set
at the signal terminals. The setting is only used, if the
SITOP UPS1600 is not in the "Remote Enable" (REN) mode
Unsigned8
0x0008: Buffering parameters (reading/writing)
Data
Description
Data type
Expected buffer current [0.1 Ah]
from V2.0 and higher
Expected buffer current: Estimated average load current during
buffer operation.
Unsigned16
0x0009: Maintenance parameters (reading/writing)
Data
Description
Data type
Resistor test interval [1 h] from
V2.1
R test interval Unsigned16
0x0010: DC-UPS command (writing)
Data
Description
Data type
CommandID
Remote reset: 8195
Unsigned16
Parameter 1
Not used
Unsigned8
Parameter 2 T
off
: output voltage down time [s]
>= V1.0
Unsigned8
Data
Description
Data type
CommandID
Remote reset 2: 8207
Unsigned16
Parameter 1
T
d
: Waiting time after end of communication [s]
Unsigned8
Parameter 2 T
off
: output voltage down time [s]
>= V2.0.0
Unsigned8
Data
Description
Data type
CommandID
Output ON/OFF: 8200
Unsigned16
Parameter 1
0
Unsigned8
Parameter 2 0: output OFF
1: output ON
Unsigned8