Engineering and remote access
3.5 Cyclic and acyclic data
SITOP UPS1600 / UPS1100
98 Manual, 04.2017, A5E37775406-8-76
Batt 6: Stop buffering voltage
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Unsigned16
Batt 6: Battery type Battery type Unsigned8
Batt 6: Minimal temperature [1 °C] Lowest specified operating temperature of the battery module
being used SITOP UPS1100.
Signed8
Batt 6: Maximal temperature [1 °C] Highest specified operating temperature of the battery module
being used SITOP UPS1100.
Signed8
Order number (Article number).
Batt 6: Manufacturing date
0x0006: Device information parameters (reading)
MLFB/order number (Article number)
0x0007: Hardware setting parameters (reading)
Buffer time [1 s] Buffer time: After the selected buffer time has expired, the
SITOP UPS1600 switches off the load output. The actual buffer
time that can be achieved depends on the connected loads and
Unsigned16
Buffer threshold [0.01 V] Connection threshold: Switching voltage for buffering. Buffering is
Unsigned16
Buffering allowed Activate or deactivate buffer operation. The setting is only accept-
ed in operating mode Remote Enable (REN) of the
Unsigned8
Enable reset Enable reset: If, during buffer operation, the input voltage be-
comes available again, then the output of the SITOP UPS1600 is
switched off for a selectable time in order to reset connected
Unsigned8