Engineering and remote access
3.5 Cyclic and acyclic data
SITOP UPS1600 / UPS1100
98 Manual, 04.2017, A5E37775406-8-76
Data
Description
Data type
Batt 6: Stop buffering voltage
[0.01 V]
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Unsigned16
Batt 6: Battery type Battery type Unsigned8
Batt 6: Minimal temperature [1 °C] Lowest specified operating temperature of the battery module
being used SITOP UPS1100.
Signed8
Batt 6: Maximal temperature [1 °C] Highest specified operating temperature of the battery module
being used SITOP UPS1100.
Signed8
Fill byte(s)
-
3 x Unsigned8
Batt 6: Order number
Order number (Article number).
VisibleString(30)
Batt 6: Serial number
Serial number
VisibleString(30)
Batt 6: Manufacturing date
Manufacturing date
VisibleString(30)
Batt 6: Version number
Version number
VisibleString(50)
0x0006: Device information parameters (reading)
Data
Description
Data type
HW revision
Hardware version
Unsigned16
SW revision
Software release
Unsigned16
Boot loader version
Boot loader version
Unsigned16
Max output current [1 A]
Maximum output current
Unsigned8
Fill byte(s)
-
Unsigned8
MLFB/Order number
MLFB/order number (Article number)
VisibleString(30)
Serial number
Serial number
VisibleString(30)
Device name
Device name
VisibleString(30)
Version number
Version number
VisibleString(50)
0x0007: Hardware setting parameters (reading)
Data
Description
Data type
Buffer time [1 s] Buffer time: After the selected buffer time has expired, the
SITOP UPS1600 switches off the load output. The actual buffer
time that can be achieved depends on the connected loads and
energy storage devices.
Unsigned16
Buffer threshold [0.01 V] Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Unsigned16
Buffering allowed Activate or deactivate buffer operation. The setting is only accept-
ed in operating mode Remote Enable (REN) of the
SITOP UPS1600.
Unsigned8
Enable reset Enable reset: If, during buffer operation, the input voltage be-
comes available again, then the output of the SITOP UPS1600 is
switched off for a selectable time in order to reset connected
loads.
Unsigned8