Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
131
Parameter assignment
With the configuration you establish which digital input data of the IM 153-2 is going to be
monitored. For the time stamping, these are signal changes on the digital inputs.
Two signal edges are always stamped. In doing so, the following assignment can be
configured:
"rising edge" (0 1) as "incoming signal"
As a result, the "falling edge" (1 0) is the "outgoing signal".
"falling edge" (1 0) as "incoming signal"
As a result, the "rising edge" (0 1) is the "outgoing signal".
Note
There are no parameters for setting the time stamping precision. To achieve the respective
precision however, the specified conditions and rules must be complied with.
8.2.2 Functionalities
8.2.2.1 Time stamp with 10 ms precision
Requirements
The 10-ms time stamping of digital input signals must be consistently supported by all the
hardware and software components: from the IM 153-2 via an automation system with its
components up to, if necessary, the operator station for the unit visualization.
The synchronization interval must be set at 10 seconds.