Interrupt, error and system messages
9.2 PROFINET IO
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
215
LEDs
Meaning
Remedy
SF
BF
MT
ON
off
off
*
on
Data exchange is taking place between
the
IO controller and the ET 200M.
The preset configuration and actual con-
figuration of the ET 200M match.
on
on
*
off
FW update busy
off
Flash
es at
0.5
Hz
*
off
FW update successfully completed
on
Flash
es at
0.5
Hz
*
off
external error during FW update
(incorrect FW, for example)
Use the correct FW for the update.
on
Flash
es at
2 Hz
*
off
internal error during FW update
(possible read/write error)
Repeat the FW update.
*
*
on
on
Loss of synchronization
Network error
Also see Maintenance interrupts
(Page 217)
LINK
RX/TX
off
off
There is no connection to the IO controller
(no IO controller available on the network)
No uniform transmission rate
Autonegotiation not successful
on
*
Autonegotiation completed and PROFINET
transmission rate accepted
on
on
Transmission/reception is in progress
* not relevant
9.2.2 Diagnostic messages of the electronic modules
Actions after a diagnosis message
Every diagnostic message leads to the following actions:
The SF LED on the interface module is lit.
There can be more than one diagnostic message at the same time.
Diagnostics data are reported as diagnosis interrupts and can be read from data records.
Following a diagnostic message, the message is saved in the diagnostic buffer of the I/O
controller.
Next, OB 82 will be called. If OB 82 is not available, the I/O controller goes to STOP mode.
Acknowledgment of the diagnostic interrupt to enable new interrupts.