Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
199
Error type
Error text
Meaning
Remedy
11101
B
29
D
Error 1 in actua-
tor / sensor
Error 1 in a an HMI device that is connected to a module.
Correction in actuator /
sensor depending on
error message, HART:
Primary value outside
of limits
11110
B
30
D
Error 2 in actua-
tor / sensor
Error 2 in a an HMI device that is connected to a module.
Correction in actuator /
sensor depending on
error message, HART:
Secondary value out-
side of limits
11111
B
31
D
Channel tempo-
rarily unavaila-
ble
e.g. due to calibration, firmware update, manual mode, etc.
Different, depending
on the cause;
e.g., wait until the
initiated function (cali-
bration, FW update) is
finished.
See also
Structure of slave diagnosis (Page 187)
9.1.3.9 H status (only with S7-400 H and normal redundancy)
Requirements
The IM 153-2 supplies the H status if
an S7-400H DP master is being worked on (IM 153-2Ax0x, IM 153-2Bx00, IM 153-2Bxx1)
standard redundant mode is being operated in (IM 153-2Bxx1 with GSD as of rev. 5)