Commissioning
6.2 PROFINET IO
ET 200M
98 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Node flash test
If you use more than one IO device, the "Assign device name" dialog also displays more than
one IO device. In this case, you should compare the MAC address of the device with the
indicated MAC address and select the proper IO device.
The identification of IO devices in a system is facilitated by a node flash test. To activate the
flash test:
1. Select one of the indicated IO devices from the "Assign device name" dialog box.
2. Select the flash period you want to use.
3. Press the "Flash on" button.
The LINK LED flashes on the selected IO device. If PROFINET IO is looped, both LINK LEDs will
flash.
6.2.4 Configuring ports of the IM 153-4 PN
Introduction
The IM 153-4 PN interface module can diagnose both of its ports: X1 P1 and X1 P2.
Requirement
The ports must be configured in HW Config.
The port diagnostics must be released.
Configuring ports in HW Config
Configure both ports of the IM 153-4 PN in HW Config in the "Properties of the IM 153-4 PN
port..." dialog:
Addresses tab:
Specify the diagnostic address of each port.
Topology tab:
Specify a "Port interconnection".
Options tab:
To enable the port diagnostics, select the following for "Connection" under "Transmission
Medium / Duplex": "Automatic Settings (monitor)".
Reference
See STEP 7 Online Help.