Interrupt, error and system messages
9
9.1 PROFIBUS DP
9.1.1 Diagnostics with LED display
Status and error displays of the IM 153-1
Table 9- 1
LEDs
Meaning Remedy
SF
BF
ON
off
off
off
No voltage on the IM 153-1 or there is a hard-
ware fault with the IM 153-1.
Switch on the power supply module or replace the
IM 153-1.
*
*
On
There is voltage on the IM 153-1.
*
flashes
on
IM 153-1 is incorrectly configured - no data
exchange is taking place between the DP mas-
ter and the IM 153-1.
Causes:
Configured and set PROFIBUS address is
incorrect
Faults on the bus
Check the IM 153-1.
Check the configuration and parameter set-
tings.
Check the PROFIBUS address on the IM 153-1
and in the STEP 7 project.
Check the cable length with reference to the
baud rate.
Check the settings for the terminating resistors.
*
on
on
no connection to the DP master (search baud
rate)
Causes:
the bus communication via PROFIBUS DP to
the IM 153-1 has been interrupted
Check the bus configuration.
Check to see if the bus connector is inserted
properly.
Check whether the bus cable to the DP master
is defective.
Switch off and on the on / off power switch for
the 24 V DC on the power supply module.
on
flashes
on
The configured structure of the ET 200M
doesn´t tally with the actual structure of the ET
200M
Check the PROFIBUS address and the configuration
of the ET 200M to see if a module is missing, faulty
or if there is a non-configured module.
Check the configuration (e.g. with COM PROFIBUS
or STEP 7).