Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
153
8.2.4.7 Structure of the IM 153-2 messages
The IM 153-2 makes available 15 data records for saving stamped input signals (signal
messages) and special messages (DS 100 to DS 114). A maximum of 20 signal and special
messages each consisting of 12 bytes can be saved in a data record.
Structure of the message frame header
Each message frame with a data record has 4 bytes of header data:
Table 8- 5 Header data of the IM 153-2 message frame (example)
Number of the data record (e.g. 100 dec.)
Number of the following bytes (e.g. 12 dec.)
Structure of the signal message
A signal message can come from modules on the slots 4 to 11. It is structured as follows:
Table 8- 6 Structure of the signal message
Meaning Number of
Remarks
module
Together with the channel number for addressing the digital signal
Slot number of the DI module
module
Together with the slot number for addressing the digital signal
Channel number of the DI module
1: Signal incoming
0: Signal outgoing
Time of the signal change
Time stamp in ISP-format
(refer to table below for structure)