6.1 PROFIBUS DP
6.1.1 Commissioning the DP slave
Software requirements
Table 6- 1 Software prerequisites for commissioning
Configuration software
Version Explanations
Configure the IM 153-x from the STEP 7 hardware catalog, then the
unrestricted S7 functionality is available (e.g removal / insertion
interrupts to the DP master with "Module change during operation"
or forwarding the configuration data to the FM or HART modules)
If your IM 153-x version is not in the hardware catalog, then inte-
grate the GSD file in STEP 7.
You have integrated the IM 153-x with the GSD-file in the
COM PROFIBUS.
COM PROFIBUS supports the GSD-file up to revision 2.
You can use the GSD-file revision ≥ 3 for the configuration, however
then the new functions of the IM 153-2Bx00 and the IM 153-2Bxx1
1
Configuration software to
the used DP master
You integrate the GSD file of the DP slave.
1
Refer to chapter "PROFIBUS DPV1 operation (Page 93)" to find out which functions can be operated with the individual
GSD revisions.
For the current GSD file, go to Internet
(http://support.automation.siemens.com/WW/view/en/113498).
Requirements for commissioning
The following conditions must be fulfilled in order to commission the ET 200M:
• DP slave installed
• PROFIBUS address set on the DP slave
• Bus connector or FOC is connected
• Only for DP interface RS 485:
If the DP slave is located on the end of the segment, then the terminating resistor is
switched on the DP slave.