Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
134 Operating Instructions, 04/2022, EWA-4NEB7806006-09
8.2.2.3 Time synchronization for time stamping
Requirements
The following requirements apply to the time synchronization for time stamping:
There must be a clock master, e.g. SICLOCK TM available in the automation system. It
must work with synchronization intervals of 10 s.
The time message frame must be forwarded:
via Ethernet e.g. to a CP 443-1
on PROFIBUS DP e.g. via an integrated DP master or CP 443-5 Extended
For the IM 153-2 (as of 6ES7153-2BAx1-0XB0) a synchronization interval of 10 s must be
configured.
Time synchonrization for highly precise time stamping with 1 ms precision
You must realize the time synchronization for the highly precise time stamping with the
following hardware components and settings:
Time master: SICLOCK TM (as of FW V3.3.0090) with GPS synchronization
Parameters to be set for SICLOCK TM:
Path / tab Parameter
(with number from the
SICLOCK parameter menu)
Value
Synchronization /
Redundancy
Synchronization
Mode (218)
Ramp
Step pos. (219)
Micro step
Step neg. (220)
Inputs
Input mode
Input type (230)
DCF
Input E1
E1 active / passive
TTY passive
DCF alarm (239)
5
Ethernet
LAN general
LAN timeout (349)
0.5 s
LAN 1-5
Adr1 protocol (e.g. 350)
Layer 2 - S5
Adr1 send (e.g. 351)
10 s
Adr1 def. (e.g. 352)
broadcast
Adr1 is given as an example. Other LAN-connections / addresses have other
parameter numbers accordingly.
LAN extra
SNTP server (550)
off
Ethernet: CP 443-1 as of FW V2.6; 6GK7443-1EX11-0XE0
Parameters to be set for Ethernet CP:
Parameter
Value
Forward time
from LAN to station
Switch on the time synchronization in SIMATIC procedure