Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
148 Operating Instructions, 04/2022, EWA-4NEB7806006-09
8.2.4.5 Configuring the time stamping
For configuring the time stamping of input signals the IM 153-2 makes available an interface
in the form of the data record 240. There you can choose your requirements accordingly,
• whether the time stamping should be generally activated / deactivated
• on which slot a module is inserted, the input signals of which should be stamped
• which signals receive a time stamp (via "DI n Enable": time stamping activated /
deactivated)
• which signal change will be stamped in which way (via "DI n Edge": "rising" edge as an
incoming signal or "falling" edge as an incoming signal).
The unselected edge is automatically the outgoing signal, i.e. both changes of a signal are
given a time stamp.
With DS_WRITE the data record 240 is transferred to the IM 153-2 for the configuration of the
time stamp.
Structure of the data record 240 for configuring the time stamp of the input signals
The telegram with the data record DS 240 has 4 bytes head data:
Figure 8-14 Head data of the telegram with the data record 240 for the configuration