8.7 Identification and maintenance data (I&M data)
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
177
8.7.2 I&M data for PROFINET IO
Reading of identification data
In STEP 7, the identification data are displayed in the "Module Information - IM 153" and
"Properties ..." tabs (see STEP 7 Online Help).
You can directly access specific identification data by selecting Read data record. Obtain the
corresponding part of the identification data under the associated data record index.
The data records are structured as follows:
Table 8- 12 Basic structure of data records with I&M data
Contents
Length (bytes)
Coding (hex)
Header information
BlockType
2
I&M0: 0020
I&M1: 0021
I&M2: 0022
I&M3: 0023
BlockLength
2
I&M0: 0038
I&M1: 0038
I&M2: 0012
I&M3: 0038
BlockVersionHigh
1
01
BlockVersionLow
1
00
Identification data
Identification data
(see table below)
I&M0 / Index AFF0: 54
I&M1 / Index AFF1: 54
I&M2 / Index AFF2: 16
I&M3 / Index AFF3: 54
The data structures in the data records correspond to the PROFINET IO definitions.