Functions
8.7 Identification and maintenance data (I&M data)
ET 200M
176 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Configuration of the I&M-data
The data structure of the I&M data corresponds to the specifications of the PROFIBUS
Guideline - Order No. 3.502, Version 1.1 May 2003.
Table 8- 11 Configuration of the I&M-data
I&M data
Access
Default
Description
Identification data 0: Index 1 (data record 231)
MANUFACTURER_ID
read (2 bytes)
2A hex (= 42 dec)
This is where the name of the manufacturer is
saved. (42 dec = SIEMENS AG)
ORDER_ID
read (20 Byte)
depending on the
module
This is where the order number of the module is
saved.
SERIAL_NUMBER
read (16 Byte)
depending on the
module
Storage location of the module's serial number.
The number allows the unambiguous identification
of the module.
HARDWARE_REVISION
read (2 bytes)
depending on the
module
This is where the version of the module is saved.
Increments when the version number or firmware
of the module alters.
SOFTWARE_REVISION
read (4 Byte)
Firmware version
Shows the module's firmware version.
If the firmware version increments, then the ver-
sion of the module also increases
(HARDWARE_REVISION).
REVISION_COUNTER
read (2 bytes)
0000 hex
reserved
PROFILE_ID
read (2 bytes)
F600 hex
Generic device
PROFILE_SPECIFIC_TYPE
read (2 bytes)
0005 hex
on interface modules
IM_VERSION
read (2 bytes)
0101 hex
Shows the I&M data version.
(0101 hex = Version 1.1)
IM_SUPPORTED
read (2 bytes)
000E hex
Shows information about the I&M data. (Index 2 to
4)
Maintenance data 1: Index 2 (data record 232)
TAG_FUNCTION
read / write
(32 bytes)
Here enter a unique identification (applicable
throughout the system) for the module.
TAG_LOCATION
read / write
(22 bytes)
Enter the location of the module here.
Maintenance data 2: Index 3 (data record 233)
INSTALLATION_DATE
read / write
(16 Byte)
Enter the installation date and, if necessary, the
respective time for the module.
RESERVED
read / write
(38 Byte)
reserved
Maintenance data 3: Index 4 (data record 234)
DESCRIPTOR
read / write
(54 Byte)
Enter a comment regarding the module here.
Changes in view of the former I&A data
Some of the content in the identification data for the I&A data has been amended in
accordance with the PROFIBUS Guideline. The access mechanism to the I&A data has been
supplemented in accordance with the PROFIBUS Guideline.