Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
198 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Table 9- 9 Error type of the channel-related diagnostic - manufacturer-specific
Error type
Error text
Meaning
Remedy
10000
B
16
D
Parameter con-
figuration error
Parameter configuration error, e.g.:
Module cannot evaluate the parameter (unknown, inad-
missible combination, ...)
Module not configured
User calibration does not correspond to the configuration
Calibration error
Correction of the pa-
rameterization
10001
B
17
D
Encoder or load
voltage missing
The following voltages could me missing:
external supply voltage
Voltage to operate the module
Correction of the pro-
cess wiring
10010B
18D
Fuse faulty
The user´s exchangeable fuse has failed
Replace the fuse
10011
B
19
D
Communication
error
With F technology (PROFIsafe):
Error with the consecutive number (sign of life)
Error in the user data CRC
User data timeout
Check the communica-
tion paths
10100
B
20
D
Ground error
Ground error, e.g.:
The permissible common mode voltage for isolated
channels has been exceeded
The M line is broken in the case of isolated channels
Correction of the pro-
cess wiring
10101
B
21
D
Reference
channel fault
Error on the reference channel
Replace the reference
channel module
10110
B
22
D
Hardware inter-
rupt lost
Hardware interrupt has become lost
Correction tuning of
program /
process / module
10111
B
23
D
Warning
There could be a warning, if limit values like:
Speed
Load current
are exceeded
Correction tuning of
program /
process / module
11000
B
24
D
Switch off
There could be a switch off:
Power switch is triggered on account of short circuit,
asymmetry, contact to earth
Thermistor triggered
Quick stop
fail-safe switch off
Remedy the cause of
switch off and
acknowledge
11001
B
25
D
fail-safe switch
off
Trigger / cause for fail-safe switch of is given
Remedy the cause of
switch off
11010
B
26
D
External error
External (process-side) error, e.g.:
Sensor error
Actuator error
Sensor data is incorrect
Replace sensor /
actuator / correct pro-
cess wiring
11011
B
27
D
Unclear error
Unclear errors are those that are not specified in any more
detail
different, depending
on cause of error
11100B
28D
reserved