Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
198 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Table 9- 9 Error type of the channel-related diagnostic - manufacturer-specific
B
D
figuration error
Parameter configuration error, e.g.:
• Module cannot evaluate the parameter (unknown, inad-
missible combination, ...)
• Module not configured
• User calibration does not correspond to the configuration
• Calibration error
rameterization
B
D
voltage missing
The following voltages could me missing:
• external supply voltage
Voltage to operate the module
cess wiring
The user´s exchangeable fuse has failed
B
D
error
With F technology (PROFIsafe):
• Error with the consecutive number (sign of life)
• Error in the user data CRC
• User data timeout
tion paths
B
D
• The permissible common mode voltage for isolated
channels has been exceeded
The M line is broken in the case of isolated channels
cess wiring
B
D
Error on the reference channel
Replace the reference
channel module
B
D
rupt lost
Hardware interrupt has become lost
program /
B
D
There could be a warning, if limit values like:
• Speed
• Load current
program /
process / module
B
D
There could be a switch off:
• Power switch is triggered on account of short circuit,
asymmetry, contact to earth
• Thermistor triggered
• Quick stop
• fail-safe switch off
switch off and
acknowledge
B
D
Trigger / cause for fail-safe switch of is given
Remedy the cause of
switch off
B
D
External (process-side) error, e.g.:
• Sensor error
• Actuator error
actuator / correct pro-
cess wiring
B
D
Unclear errors are those that are not specified in any more
detail
different, depending
on cause of error