Interrupt, error and system messages
9.2 PROFINET IO
ET 200M
214 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Status and error displays SF, BF, ON, LINK, RX/TX
Table 9- 10 Status and error displays of the IM 153-4 PN
LEDs
Meaning
Remedy
SF
BF
MT
ON
off
off
off
off
There is no voltage at the interface mod-
ule, or the interface module has a hard-
ware defect.
Switch on the 24 VDC supply voltage at
the interface module.
*
*
*
On
There is voltage at the interface module.
*
Flash
es at
0.5
Hz
*
on
Faulty or no connect message frame - no
data transfer between the IO controller
and the interface module (IO device),
although the device is physically connect-
ed to the switch.
Causes:
Incorrect device name
Configuration error
Programming error
The IO controller is disconnected,
defective or the bus cable to the con-
troller is missing.
The backplane bus is not functional.
Check the interface module.
Check the configuration and parameter
settings.
Check the device name.
Assign a valid device name to the inter-
face module.
Check the IO controller
Check to see if the backplane bus has
been configured correctly (all modules
inserted, terminating resistor installed)
*
on
*
on
The IO device is not connected to a switch.
Establish a connection to the IO control-
ler (via a switch).
Assign a valid device name to the inter-
face module.
Check the bus configuration.
Check that the bus connector is correctly
inserted.
Check whether the bus cable to the IO
controller is interrupted.
on
*
*
on
The configured structure of the ET 200M
does not match the actual structure of the
ET 200M.
Check the structure of the ET 200M,
whether a module is missing or defec-
tive, or whether an unconfigured mod-
ule has been inserted.
Check the configuration (using STEP 7,
for example), and correct the parameter
assignment errors.
There is an error in an I/O module, or
the interface module is defective.
Diagnostics data available
Replace the interface module, or get in
touch with your Siemens contact part-
ner.
Remove error, e.g. wire break
on
on
*
on
A new SIMATIC Micro Memory Card is
currently being formatted.
Wait until the formatting sequence is
complete. This may take several
minutes. If the LED behavior changes,
the formatting process is complete.