Functions
8.6 Isochrone mode
ET 200M
170 Operating Instructions, 04/2022, EWA-4NEB7806006-09
2. Settings on the DP master system:
"Object properties" of the DP master > tab "General" > button "Properties" > tab
"Parameters" > button "Properties" > tab "network settings" > button "Options"
Enabling equidistance on the DP master system
Set the length of the equidistant DP cycle (max. 32 ms)
Set "Times Ti and To same for all slaves" (causes a synchronization of the input / output
data for the various DP slaves)
The times Ti and To can be set separately.
Recommendation: Adopt the standard settings for Ti and To.
Figure 8-22 Options dialog box
Note
With the button "Recalculation" you can calculate with
STEP 7 a value for the
equidistant DP cycle, which takes into account the current PROFIBUS DP.
This value is then automatically entered in the fields "E
quidistant DP cycle", "Time Ti
(…)" and "Time To ()".