Brief instructions on commissioning
2.1 Commissioning on PROFIBUS DP
ET 200M
32 Operating Instructions, 04/2022, EWA-4NEB7806006-09
SM 322: Short-circuit to L+
1. Open the front panel of the DO-module and use a wire to short circuit the digital output 0
(terminal 3) after L+ (terminal 1).
2. Note the status LEDs.
IM 153-2:
SF: ON
SM 322; DO 8 x DC 24 V/0,5 A:
SF: lights up a diagnostic message is pending
F0: light up channel error
0: OFF Output is not active
3. Evaluate the diagnostic message.
Result:
Station status 1 Byte x.3 is set external diagnostics
Identifier-related diagnostics: Byte (x+7).4 is set Slot 5
Channel-related diagnostics:
Byte (x+16).0 to (x+16).5: 000100
B Slot 5
Byte (x+17).0 to (x+17).5: 000000
B Channel 0
Byte (x+18).0 to (x+18).4: 00001
B Short circuit
4. Remove the wire between terminal 3 and terminal 1.
Evaluate the diagnosis LEDs once again.
IM 153-2:
SF: off
SM 322; DO 8 x DC 24 V/0,5 A:
SF: off
F0: off
0: On
The diagnostic message is deleted.
See also
Diagnosis with STEP 7 or STEP 5 (Page 184)

Table of Contents