Commissioning
8.7 Commissioning optional additional modules
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
335
You can also subsequently activate option module CBE20.
Start the configuration wizard via "Control Unit" -> Configuration" -> "Wizard..."
In the "Option module" screen form, select CBE20
Work through the remainder of the wizard up to the end
Go online
Load the project to the drive
8.7.3.3
Deleting from the drive online
Removing a CBE20 without STARTER always leads to the loss of the parameter
assignments which are replaced by the factory settings.
p0009 = 30
p0976 = 1
(recent commissioning)
8.7.3.4
Deleting offline with STARTER
CBE20 can only be removed in the offline state.
Start the configuration wizard via "Control Unit" -> Configuration" -> "Wizard..."
In the "Option module" screen form, deselect CBE20
Work through the remainder of the wizard up to the end
Remove the CBE20 option board from the Control Unit
Go online
Load the project to the drive