EasyManua.ls Logo

Siemens 6RA8085-6DS22

Siemens 6RA8085-6DS22
758 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
8.9 Manual optimization
SINAMICS DCM DC Converter
346 Operating Instructions, 12/2018, A5E34763375A
8.9.2
Optimization of closed-loop field-current control
Determining the field circuit resistance (2 options)
1.
Roughly estimate the field circuit resistance from the rated motor data
p50112 = rated excitation voltage/rated excitation current of motor
2.
Determine the field-circuit resistance by comparing the field current setpoint and actual
value
-
p50112 = 0: Results in a 180° field precontrol output and, therefore, field current
actual value = 0
-
p50082 = 3: So that the field remains permanently switched on, even when the line
contactor drops out
-
p50254 = 0 and p50264 = 0: Only field precontrol active; field-current controller
disabled
-
Set p50102 to rated excitation current.
-
Increase p50112 until the actual field current (r50035 converted to amperes using
r50073[1]) equals the required setpoint (p50102).
-
Set p50082 back to the system's operating value.
Overall optimization of closed-loop field-current control
Checking the precontrol characteristic
Procedure
-
Set the function generator to a triangular waveform (0% to 100%), period =
10000 ms
-
Supply point: p50611[0] (see function diagram 6905)
-
Set p50082 = 3 (field continuously on)
-
Record the signals r52271 (output, precontrol) and r52260 (output, field current
controller)
-
The parameters of the precontrol (Rf [p50112], Lf [p50116] and λf [p51597]) have
been correctly set if the output of the field controller has the lowest possible value
(e.g. less than 5%) over the complete setpoint range.
Checking the step response
Procedure
-
Set the function generator to a squarewave, with
step
height = e.g. 5%
offset = various values, e.g. 80
%
period = 1000
ms
pulse width = 500 ms
-
Supply point: p50611[0] (see function diagram 6905)
-
Set p50082 = 3 (field continuously on)
-
Record signals r52268 (If-set) and r52265 (If-act)
-
Change controller parameters Kp (p50255) and Tn (p50256) until the step
response provides a satisfactory result.
-
The field current controller adaptation can be activated (see function chart 6908) to
eliminate the influence of non-linearity of the field inductance and gating unit.

Table of Contents

Related product manuals