Descriptions of functions
10.8 Communication via Modbus TCP
SINAMICS DCM DC Converter
538 Operating Instructions, 12/2018, A5E34763375A
10.8
Communication via Modbus TCP
10.8.1
Overview
The Modbus protocol is a communication protocol based on a controller/device architecture.
Modbus offers three transmission modes:
Modbus ASCII
Via a serial interface
Data in the ASCII code. The data throughput is lower compared to RTU.
Modbus RTU
Via a serial interface
Data in the binary format. The data throughput is greater than in ASCII code.
Modbus TCP
Via Ethernet
Data as TCP/IP packages. TCP port 502 is reserved for Modbus TCP.
Only transfer type "Modbus TCP" is available for SINAMICS DCM.
Modbus functionality
Process data and parameters are accessed via the Modbus register.
Process data: 40100 - 40119
A maximum of 10 process data (PZD) can be exchanged.
Drive data: 40300 - 40522
All parameters via DS47: 40601 - 40722
Modbus TCP always provides a basic Ethernet functionality, which corresponds to the
functionality of Ethernet interface X127:
Commissioning access for STARTER/Startdrive with S7 protocol
DCP (Discovery and Configuration Protocol) to set the IP address etc.
SNMP for identification
General information about communication
Communication with Modbus TCP uses the Ethernet/PROFINET interface:
X1400
:
For Modbus TCP with a CUD via a CBE20.
The following applies for the CUD:
An advanced CUD must be inserted.
The memory card (with the device firmware) must be inserted.