1. Select 'Commissioning' > 'Download site' in SintesoWorks.
The 'Download site' and 'Connect' windows open in SintesoWorks.
2. Select the connection in the 'Connect' window and click on 'OK'.
The 'Stations' are listed in the 'Download site' window.
3. Select the 'Stations' whose configuration you would like to load from
'SintesoWorks' to the 'Stations' and click on 'Start'.
The 'PathProvider configuration is missing.' window may open in
SintesoWorks with the 'Combination Resource type/Resource ID is not
registered!' prompt. Press <MENU> on the 'Station', enter the PIN and
press <ok>.
4. Click on 'OK' in the 'PathProvider configuration is missing.' window in
SintesoWorks.
The 'Action confirmation' window opens in SintesoWorks.
5. Click on 'Yes'.
The configuration is loaded to the 'Station'.
The progress is displayed in the 'Download site' window in SintesoWorks.
The 'Station' restarts.
After a few minutes, the 'Buzzer' sounds twice at the 'Station'.
6. Press <Acknowledge> on the ↑ Person Machine Interface at the 'Station' to
switch off the 'Buzzer'. Do not perform any more actions on the 'Station' until
the 'Buzzer' has sounded for the second time.
You will find more information about 'Loading configuration from the PC to the
station' in document '009078', see 'Applicable documents [➙ 6]'.