Page 136 HydroRanger 200 – INSTRUCTION MANUAL 7ML19985FC03
mmmmm
Parameters
P113 Relay OFF Setpoint
Sets the process point at which the relay returns to its NORMAL state.
For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the low point in the specified range. This parameter is set to Span
(P007), even when another reading, such as volume, is shown on the LCD.
P115 Relay Interval Setpoint [6 relay model]
The length of time in hours between starts.
P116 Dead Band [6 relay model]
The distance above and below the bound alarm setpoints.
Primary Index Relay
Values
Range: -999 TO 9999
Preset: ----
Altered by •P007 Span
Related
P100 Preset Applications
P111 Relay Control Function
P112 Relay ON Setpoint
Primary Index Relay
Values
Range: 0 to 9000
Preset: 0.000
Altered by P100 Preset Applications
Related P111 Relay Control Function
Primary Index Relay
Values
Range: 0.000 to Span Value (P007), or equivalent depending on units
Preset: 2% of span
Related
P111 Relay Control Function
P112 Relay ON Setpoint
P113 Relay OFF Setpoint