Parameters
Independent mA Setpoints (P210 and P211)
Use these features to reference the minimum and/or maximum mA output to any point in
the measurement range.
P210 0/4 mA Output Setpoint
Sets the process level corresponding to the 0 or 4mA value.
Enter the value (in applicable units or %) to correspond to 0 or 4 mA.
P211 20 mA Output Setpoint
Sets the process level that corresponds to the 20 mA value.
Enter the value (in applicable units or %) to correspond to 20 mA.
mA Output Limits (P212 and P213)
Use these features to adjust the minimum and/or maximum mA output values, which
should suit the input limit requirements of the external device.
P201—mA Function
Settings
Action
Level, Space, or Distance
Enter the material level in Units (P005) or percent of
Span (P007) as referenced to Empty (P006).
Volume [6 relay model]
Enter the volume in Max Volume (P051) units or as a per-
cent of Max Volume.
Flow [6 relay model]
Enter the flowrate in OCM Max Flow (P604) units or as a
percent of OCM Max Flow.
Head [6 relay model]
Enter the head in level units (P005) or percent of Max
Head (P603).
Volume Rate [6 relay model]
Enter the volume rate in volume/min. Ensure the % sym-
bol is displayed before attempting to enter a % value.
mA input or
Communications Input
Not Applicable
Primary Index mA output
Values Range: -999 to 9999
Related P211 20 mA Output Setpoint
Primary Index mA output
Values Range: -999 to 9999
Related P210 0/4 mA Output Setpoint