7ML19985FC03 HydroRanger 200 – INSTRUCTION MANUAL Page 153
mmmmm
Parameters
P260 mA Raw Input [6 relay model]
Shows the raw mA input supplied by the external device.
Discrete Input Functions (P270 to P275)
Discrete inputs can be used for the following:
Passing other information to a remote system through communications
Backup level override
Use the parameters listed above to have discrete inputs modify the unit’s operation.
Use the following parameters to configure the discrete input itself.
See also the
Pump Control
section on page 56 for a description of the HydroRanger 200’s
pump control algorithms, including how the discrete inputs alter its operation.
P270 Discrete Input Function
Sets how discrete signals are interpreted by the HydroRanger 200.
Primary Index mA input
Values Range: 0.000 to 20.00 (view only)
Primary Index Discrete input
Values
0Forced OFF
1Forced ON
2 * Normally Open – 0 (DI open), 1 (DI closed)
3 Normally Closed – 0 (DI closed), 1 (DI open)
Related Pump Control section