7ML19985FC03 HydroRanger 200 – INSTRUCTION MANUAL Page 51
mmmmm
Volume
HydroRanger 200 [6 relay model]
Parameter Transducer Index Value Description
P054 1
10.0
Determines the Level breakpoints at
which the volumes are known.
20.8
32.0
43.5
54.1
64.7
75.1
85.2
95.3
10 5.4
11 5.5
12 5.6
13 6.0
14 7.2
15 9.0
P055 1
10.0
Determines the volumes which
correspond to the level breakpoints.
The universal calculations interpret
between the breakpoints to produce
an accurate model of the volume at
all level readings.
Settings
P050 = 9 for linear approximation
P050 = 10 for curved approximation
Linear approximation uses a linear
algorithm; curved approximation
uses a cubic spline algorithm.
22.1
34.0
45.6
55.9
66.3
76.7
87.1
97.8
10 8.2
11 8.8
12 9.2
13 10.9
14 13.0
15 15.0