Page 174 HydroRanger 200 – INSTRUCTION MANUAL 7ML19985FC03
mmmmm
Parameters
Pumped Volume Totalizer (P622) [6 relay model]
The Pumped Volume Totalizer is a feature of the HydroRanger 200 6 relay model only.
If the eight-digit totalizer display or a remote totalizer contact closure are desired, alter
the following parameters.
P622 Inflow / Discharge Adjust [6 relay model]
The method used to calculate the volume pumped, for pumped total Operation (P001 = 7).
* or discharge
Primary Index
Single Point Model Dual Point Model
Global Transducer
Values
1 = inflow * / pump cycle
When the pump is off, the HydroRanger 200 estimates the volume of
inflow by recording the rate at which the liquid level changes. When
the pump is operating, the estimated inflow volume is added to the
pumped volume total. When the pump stops, the pumped volume of
the previous pump cycle is added to the total volume pumped in the
totalizer.
2 = inflow * ignored
Inflow is assumed to be 0 while pumps are running.
3 = inflow * / rate (preset)
Volume pumped is adjusted for inflow. Inflow rate is estimated by
assuming that the rate calculated (P708) just prior to the start of the
pump cycle remained constant during the pump cycle. Inflow rate is
averaged using rate filter (P704), rate update time (P705) and rate
update distance (P706) to control how the average rate is calculated.
Related
•P001 Operation
P704 Rate Filter
P705 Rate Update Time
P706 Rate Update Distance
P708 Volume Rate Display