Page 144 HydroRanger 200 – INSTRUCTION MANUAL 7ML19985FC03
mmmmm
Parameters
P171 Flush Cycles [6 relay model]
Sets the number of pump cycles requiring flush control.
If three flush cycles are required after every ten pump cycles then:
P172 (Flush Interval) = 10
P171 (Flush Cycles) = 3
P172 Flush Interval [6 relay model]
Sets the number of pump cycles before flush control is enabled.
To start a new flush cycle every ten times the pumps are run, set this to 10.
P173 Flush Duration [6 relay model]
The length of time for each flush cycle that the flush control is active.
Primary Index
Single Point Model Dual Point Model
Global Relay
Values
Range: 0 to 9999
Preset: 0
Related P111 = 64, Flush Valve
Primary Index
Single Point Model Dual Point Model
Global Relay
Values
Range: 0 to 9999
Preset: 0
Related P111 = 64, Flush Valve
Primary Index
Single Point Model Dual Point Model
Global Relay
Values
Range: 0.000 to 9999 s
Preset: 0.000
Related P111 = 64, Flush Valve