Page 146 HydroRanger 200 – INSTRUCTION MANUAL 7ML19985FC03
mmmmm
Parameters
HydroRanger 200 [6 relay model]
P202 mA Output Allocation
Sets the input source from which the mA output is calculated.
Please note that parameter P202 values vary between the HydroRanger 200, 1 or 3 relay
model, and the HydroRanger 200, 6 relay model.
HydroRanger 200 [1 or 3 relay model]
HydroRanger 200 [6 relay model]
Primary Index mA output
Values
value mA function Operation (P001)
0OFF
1 level level, differential, or average
2space space
3 distance distance
4 volume level or space
5flow OCM
6head
7 volume rate
8mA input
9 comms input
Related
P202 mA Output Allocation
•P911 mA Output Value
Altered By •P001 Operation
Primary Index mA output
Values 1* Point 1
Related P201 mA Output Function
Primary Index mA output
Values
1*Point 1
2 Point 2
1:2 Average of readings from Point 1 and Point 2
3 Point 3
Related P201 mA Output Function