EasyManua.ls Logo

Siemens LMV36.520 Series - Page 122

Siemens LMV36.520 Series
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
122/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 12 Actuators X53 / X54 25.09.2013
No. Parameter
601
Selection of reference point
Index 0 = fuel
Index 1 = air
0 = closed (<0°)
1 = open (>90°)
602
Actuator's direction of rotation
Index 0 = fuel
Index 1 = air
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
606
Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
error detection band: (parameter 606 -0.6°) up to parameter 606
608
Fuel 1: Selection of reference point
0 = closed (<0°)
1 = open (>90°)
609
Fuel 1: Actuator's direction of rotation
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
610
Fuel 1: Tolerance limit of position monitoring (0.1°)
Index 0 = fuel
Index 1 = air
Greatest position error where an error is securely detected
Error detection band: (P606 -0.6°) up to P606
611
Type of reference
Index 0 = fuel
Index 1 = air
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1…)
3 = both
612
Fuel 1: Type of reference for fuel actuator
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1…)
3 = both
613 Type of actuator
Index 0 = fuel
Index 1 = air
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
614 Fuel 1: Type of actuator
0 = 5 s / 90° (1 Nm, 1,2 Nm, 3 Nm)
1 = 10 s / 90° (6 Nm)
2 = 17 s / 90° (10 Nm)
Application note!
Single-sided load torque is recommended due to the type of gear train for the
SQM33.6 / SQM33.7 actuators. In the event of load on both sides, a backlash of 0.3°
must also be considered in addition to plant design or setting

Table of Contents