190/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
28.10 Parameters with index, with no direct display
28.10.1 Using the example of parameter 701: Errors
Refer to chapter Error code list!
Note
Can be deleted for service, refer to chapter Parameter list!
P
Vhmins%
Bild 84/0707
HIStorie 700: for error history.
reset
Press
reset
to go to the
parameter level.
P
Vhmins%
Bild 85/0707
Press to select parameter 701.
Display: Parameter 701. flashes, index 01: and value 201
do not.
reset
P
Vhmins%
Bild 86/0707
Press
reset
to go to index 01:.
Display: Parameter 701. does not flash, index 01:
flashes, value 201 does not.
To the next index
Back to the previous
index
P
Vhmins%
Bild 87/0707
Press
to select the index:
.01 = error code
.02 = diagnostic code
.03 = error class
.04 = error phase
.05 = startup counter
.06 = output
Example:
Parameter 701., index 05: for startup counter, diagnostic
code
._._