EasyManua.ls Logo

Siemens LMV36.520 Series - Gas; Oil Pressure Switch-Max (Pmax); or POC Contact, Start Release Oil X5-02

Siemens LMV36.520 Series
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 7 Basic unit 25.09.2013
7.3.9 Gas / oil pressure switch-max (Pmax) / or POC contact, start
release oil X5–02
Input for connection of a pressure switch-max for gas or oil: The sensor must have an
NC contact, which means that the contact opens when the adjusted maximum pressure
is exceeded. If the plant does not require a pressure switch-max, a wire link must be
fitted between pin 2 and 3.
Caution!
The OEM must check to see whether the burner can be operated without
pressure switch-max. This may necessitate a special approval, depending on
the type of application.
LMV...
Bild 279e/1010
X5-02
Pmax/POC
Protective earth (PE)
Pressure switch-max or POC
“L” for pressure switch
Figure 25: LMV36...: Gas / oil Pressure switch-max (Pmax) or POC X5-02
LMV...
Bild 280e/1010
X5-02
Protective earth (PE)
Pressure switch-max or POC
“L” for pressure switch
AGM60...
V3
Oil
max
P
Gas
max
P
3
2
1
1
2
3
1
2
3
1
2
3
4
5
Figure 26: LMV36... with AGM60…: Gas / oil pressure switch-max (Pmax) or POC X5-02