24.1.4 Fault status messages, display of errors and info
24.1.4.1. Display of errors (faults) with lockout
P
Vh
mi n
s%
Bild 17/0707
The display shows Loc:, the bar under the fault status
message
appears.
The unit is in the lockout position.
The display shows current error code c: alternating with
diagnostic code d: (refer to Flash code list).
Example: Error code 4 / diagnostic code 3
P
Vh
mi n
s%
Bild 18/0707
24.1.4.2. Reset
reset
1…3 s
P
Vh
mi n
s%
Bild 19/0707
Press
reset
for 1...3 s so that rESEt appears on the display.
When you release the button, the basic unit is reset.
If you press
reset
for >1 s or <1 s, the system returns to the
former menu.
Exception:
If a fault occurs in connection with the curve setting, the
system returns to the parameter setting level.
24.1.4.3. Activating info / service mode from lockout
reset
>3 s
Press
reset
for >3 s so that InFo, SEr and then OPErAtE
appear on the display.
When the button is released, a change to info / service
mode is made.
reset
>5 s
P
Vh
mi n
s%
Bild 21/0707
reset
>8 s
P
Vh
mi n
s%
Bild 22/0707