Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 28 Parameter level 25.09.2013
F
and
A
and
or
P
Vh
s
min %
Bild 110/0807
Press simultaneously
F
and
A
and
or to adjust speed n0 of the VSD.
Example: 20.0
P
Vh
s
min %
Bild 111/0807
Release
F
and
A
.
The selected value is adopted.
Example: 20.0
To the next curvepoint
P
Vh
mi n
s%
Bild 112/0707
Press
.
P9 appears blinking.
Curvepoint for high-fire.
Same procedure as with P0
Note
If
is pressed first, the display jumps to
90!
To the next curvepoint
Back to the previous
curvepoint
P
Vh
mi n
s%
Bild 113/0707
Press
.
The display shows run (identification of start
for setting the curve parameters).
The display shows run Gas0 or run Gas1 or
run Oil0 or run Oil1, depending on the type
of fuel currently burnt or the type of fuel train.
Note
When pressing
/
reset
, you are given the choice of proceeding with the warm settings
(refer to chapter Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2
mod» and «Lo mod») or, by pressing
ESC
, with the cold settings (refer to
chapters Cold settings for «G mod», «Gp1 mod», «Gp2 mod» and «Lo mod»).
28.11.3 Setting curvepoints P0 and P9 for «G mod pneu», «Gp1 mod pneu»
and «Gp2 mod pneu»
Note
Refer to chapter Setting curvepoints P0 and P9 for modulating operation («G mod», «Gp1
mod», «Gp2 mod» and «Lo mod»)! Here, only the air requires adjustment with
A
.

Table of Contents

Other manuals for Siemens LMV36.520 Series