Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 27 Service level 25.09.2013
27 Service level
The service level is used to display information about errors including the error history and information about
the basic unit.
Note
When on the service level, you can press or to display the next or the previous
parameter.
Instead of pressing , you can also press
/
reset
for <1 s.
Note
Press
ESC
or
/
reset
for >3 s to return to the normal display.
Note
P
Vh
min s %
Bild 39e/0807
Parameter
Parameter value
Figure 97: Service level
No change of values on the service level.
If characters are displayed by the parameter, the value may consist of more than 5 digits.
Press
/
reset
for >1 s and <3 s to display the value.
Press
/
reset
for >3 s or
ESC
to return to the selection of the parameter (flashing).
27.1 Display of service level
/
reset
P
Vh
mi n
s%
Bild 21/0707
Press
/
reset
for >3 s until SEr appears.
When releasing
/
reset
, you are on the service level.
No. Parameter
Service level
954 Intensity of flame
960 Actual flow rate (fuel throughput in m³/h, l/h, ft³/h, gal/h)
945 Actual fuel
0 = fuel 0
1 = fuel 1
121 Manual output
Undefined = automatic operation
922 Incremental position of actuators
Index 0 = fuel
Index 1 = air
936 Standardized speed
161 Number of faults
701 Error history: 701-725.01.Code