28.7 Parameters without index, with direct display
28.7.1 Using the example of parameter 208: Program stop
PArAmeter level 200: for basic units.
/
reset
Press
/
reset
to go to menu
level 200:
P
Vh
mi n
s%
Bild 64/0707
Press to select Program stop.
Display: Parameter 208: flashes, value 0 does
not.
/
reset
P
Vh
mi n
s%
Bild 65/0707
Press
/
reset
to go to editing mode.
Display:
Program stop time set
Here: Value 0
corresponding to program stop
deactivated.
or
P
Vh
mi n
s%
Bild 66/0707
Press
or to select the required
program stop time.
0 = inactive
1 = PrePurgP (Ph24)
2 = IgnitPos (Ph36)
3 = Interv1 (Ph44)
4 = Interv2 (Ph52)
Example: 2 IgnitPos (Ph36)