127/248 
Building Technologies Division  Basic documentation LMV36...  CC1P7544en 
Infrastructure & Citiies Sector  12 Actuators X53 / X54  25.09.2013 
 
No. Parameter 
606 
Tolerance limit of position monitoring (0.1°) 
Index 0 = fuel 
Index 1 = air 
Greatest position error where an error is securely detected  
 error detection band: (parameter 606 -0.6°) up to parameter 606 
610 
Fuel 1: Tolerance limit of position monitoring (0.1°) 
Index 0 = fuel 
Index 1 = air 
Greatest position error where an error is securely detected  
 error detection band: (parameter 606 -0.6°) up to parameter 606 
 
Error 
code 
Diagnostic 
code 
Meaning for the LMV36... system 
86  0 Fuel actuator: Position error 
87  0  Air actuator: Position error