Figure 99: Setting the curvepoints 
 
 
Note 
Curvepoints P2 to P8 are automatically computed as a straight line between P1 and P9. 
 
Example 1 = gas modulating 
 
P0, P1 and P9 are set as described: Curvepoint Value 1 
fuel 
Value 2 
air 
P0 
30.0 22.0 
P1 
32.0 24.0 
P9 
80.0 90.0 
 
P2 through P8 have automatically been  
calculated: 
Curvepoint Value 1 
fuel 
Value 2 
air 
 P2 38.0 32.3 
P3 
44.0 40.5 
P4 
50.0 48.8 
P5
56.0 57 
P6 
62.0 65.3 
P7 
68.0 73.5 
P8
74.0 81.8