206/248 
Building Technologies Division  Basic documentation LMV36...  CC1P7544en 
Infrastructure & Citiies Sector  28 Parameter level  25.09.2013 
 
F
 and 
A
 
and 
 or   
P
Vhsmin%
Bild 139/0807
 
Press 
 or   to change the value as  
required. 
Example: 00.0 
 
F
 or 
A
 
P
Vhmins%
Bild 140/0707
 
Release 
F
 or 
 . 
 
The required value is adopted. 
 
Example: P5:50.0:46.0 
 
 
>3 s 
P
Vh
mi n
s%
Bild 124/0707
Keep   depressed for >3 s. 
 
CALC appears. 
 
 
P
Vhmins%
7´Bild 141/0707
The display jumps to P6. 
 
All curvepoints from P5 to P9 have now been 
automatically recalculated (linear interpolation): 
Curvepoint Value 1 
fuel 
Value 2 
air 
P5 
50.0 46.0 
P6 
57.5 57.0 
P7 
65.0 68.0 
P8 
72.0 79.0 
P9 
80.0 90.0 
 
 
>3 s 
P
Vh
mi n
s%
Bild 124/0707
Keep   depressed for >3 s. 
 
CALC appears. 
 
 
P
Vhmins%
Bild 142/0707
The display jumps to P4. 
 
All curvepoints from P1 to P5 have now been 
automatically recalculated (linear interpolation): 
Curvepoint Value 1 
fuel 
Value 2 
air 
P5 
50.0 46.0 
P4 
45.5 40.0 
P3 
41.0 35.0 
P2 
36.5 29.5 
P1 
32.0 24.0