243/248
Building Technologies Division Basic documentation LMV36... CC1P7544en
Infrastructure & Citiies Sector 30 Error code list 25.09.2013
Error
code
Diagnostic code Meaning for the LMV36... system Remedy
Communication breakdown was interrupted for more than 30 seconds
33
Manual locking by the PC software
Test of lockout
PC software made a reset attempt with an error-free system
168 # Internal error management
Make a reset; if error occurs repeatedly, replace the unit
169 # Internal error management
Make a reset; if error occurs repeatedly, replace the unit
170 # Internal error management
Make a reset; if error occurs repeatedly, replace the unit
171 # Internal error management
Make a reset; if error occurs repeatedly, replace the unit
200 OFF # System error-free
No error
201 OFF
UPr0
or
OFF UPr1
# Prevention of startup
Start prevention due to unparameterized unit
Go to error history, entry 702, for initial cause of the error with shutdown in connection with the first
curve settings
Bit 0
Valency 1
No operating mode selected
Bit 1
Valency 2..3
No fuel train defined
Bit 2
Valency 4..7
No curves defined
Bit 3
Valency 8..15
Standardized speed undefined
Bit 4
Valency 16..31
Backup / restore was not possible
202 # Internal error operating mode selection
Redefine the operating mode (parameter 201)
203 # Internal error
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the unit
204 Phase number Program stop
Program stop is active (no error)
205 # Internal error
Make a reset; if error occurs repeatedly, replace the unit
206
0 Inadmissible combination of units (basic unit – AZL2...)
207 # Version compatibility basic unit – AZL2...
0 Basic unit version too old
1 AZL2... version too old
208 # Internal error
Make a reset; if error occurs repeatedly, replace the unit
209 # Internal error
Make a reset; if error occurs repeatedly, replace the unit
210
0 Selected operation mode is not released for the basic unit Select a released operation mode for the basic unit
240 # Internal error
Make a reset; if error occurs repeatedly, replace the unit
245 # Internal error
Make a reset; if error occurs repeatedly, replace the unit
250 # Internal error
Make a reset; if error occurs repeatedly, replace the unit