Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default
parameter
setting
LMV51 LMV52
125/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
StartReleaseGas Input start release oil active deactivated
activated
OEM activated x
StartReleaseOil Input start release oil active deactivated
activated
OEM activated x x
AirPressureTest Assess/ignore air pressure signal deactivated
activated
OEM activated x x
PS-VP/CPI Configuration of input on PM-VP or CPI PS-VP
CPI
OEM PS-VP x x
FGR-PS/FCC Configuration of input for FCC or FGR-PS FCC
FGR-PS
deactivated
OEM FCC x x
InputController Input controller active deactivated
activated
OEM activated x x
GasPressureMin Input minimum gas pressure (+start release gas) active deactivated
activated
deact xOGP
OEM activated x x
GasPressureMa
x
Input maximum gas pressure active deactivated
activated
OEM activated x x
OilPressureMin Input minimum oil pressure active deactivated
activated
act from ts
OEM activated x x
OilPressureMax Input oil pressure max. active deactivated
activated
OEM activated x x
HeavyOilDirStart Input immediate heavy oil start active deactivated
activated
OEM activated x x
Start/PS-Valve Configuration of output for start signal or PS relief valve StartSignal
PS Relief
PS Reli_Inv
OEM StartSignal x x
ConfigFlameDet Configuring the flame detector OEM x x
ReacExtranLight Reaction in the event of extraneous light in standby Lockout
Startblock
OEM Startblock x x
FlameSignal Configuration the flame signal OEM x x