LMVSeries TechnicalInstructions
 LV51000
SCCInc. Page49 Section3
13) Actuatorpositionischeckedby using oneofthreemethods.Themethoduseddependsupon the phaseofthesequence.
PositionRequiredtoProceedmeansthattheactuatorsmustachieveandholdacertainpositionforthesequencetoproceed.
DynamicPositionCheckingmeansthattheactuatorisevaluatedbya“timeanddistancefromtargetalgorithm.Thefurther
theactuatorisawayfromitstargetposition,thelesstimetheactuatorispermittedtobeinthatposition.RunTimePosition
Checkingmeansthattheactuatorisexpectedtobeatacertainpointinacertainamountoftime(basedoffoftheruntime
oftheactuator).
14) For direct spark oil fuel trains, spark (ignition) will occur during prepurge if parameter OilPumpCoupling is set to
MagnetcouplandparameterIgnOilPumpStartissettooninPh22.
15) IfparameterFGRPS/FCCissetforPSdeactStby,thestatusoftheFGRpressureswitchisnotcheckedinphase10or12.The
restofthesequenceisthesameassettingthisparametertoFGRPS.IfparameterFGRPS/FCCissetforPSVSD,inputX4
01.3mustbeenergizedanytime theVSD speedishigherthanRotSpeedPSonandde energizedanytimetheVSD speedis
lowerthanRotSpeedPSoff.
16) DependingonhowparameterHeavyOilDirStartisset,inputX601.3hasvaryingsequences.Ifthisparameterissetforactiv
38/44,input X601.3mustbeenergizedinphase44.Ifthisparameterissetfor38/44..62,inputX601.3mustbeenergized
inphases4462.Ifthisparameterissetforact21..62,inputX601.3mustbeenergizedinphases2162.Ifthisparameteris
setfordeactivated,energizinginputX601.3hasnoeffect.
17) Inputs X503.2 and X503.3 have many functions depending on how parameter Config X503 is set.The settings are as
follows:
LMV5x std If parameter LC_OptgMode is set to ExtLC X503, energizing X503.2 will decrease the firing rate, while
energizingX503.3willincreasethefiringrate.
LMV2/3stdIfparameterLC_OptgModeissettoExtLC X503,energizingX503.3willachievestage2oil,whileenergizing
X503.2willachievestage3oil.
LMV2/3invIfparameterLC_OptgModeissettoExtLC X503,energizingX503.2willachievestage2oil,while energizing
X503.3willachievestage3oil.