EasyManua.ls Logo

Siemens LMV51.140C1 - Page 108

Siemens LMV51.140C1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeries TechnicalInstructions
 LV51000
SCCInc. Page50 Section3
DeaO2/Stp36 Energizing input X503.2 disables O
2
trim, while deenergizing X503.2 enables O
2
trim (LMV52 only).
EnergizinginputX503.3allowstheLMV5toprogresspastphase36.IfX503.3isdeenergized,theLMV5willremain
inphase36indefinitely.
CoolFctStbyThissettinghasnoeffect(LMV50only).
AutoDeactO2 Energizing input X503.3 will deactivate O2 trim by setting O2 trim OptgMode to auto deact.O2 trim
OptgModemustbesettoConAutoDeacforthisfunctiontowork.DeenergizingX503.3setstheO2trimOptgMode
backtoConAutoDeac.TerminalX503.2hasnofunctionwiththissetting.
HOME
HOME
HOME

Table of Contents

Other manuals for Siemens LMV51.140C1

Related product manuals