TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section4 Page8 SCCInc.

Driveto
IgnitionPos.
Preignition
(SPARK)=ON
PilotValve=ON
IGN(SPARK)=OFF
Interval1(Pilot
Stabilization)
SafetyTime2
Interval2(Main
Stabilization)
Driveto
LowFirePos.

36 38 40 42 44 50 52 54
Terminal Description
SAFETYTIME
1
DirectIgniG
X402.3 Ignition
X901.4
GasvalveV1(mainvalve,
upstream)
X901.3
GasvalveV2(mainvalve,
downstream)
PilotGp1
X402.3 Ignition
X901.1
GasvalveSV(safetyvalve,
usuallyoutdoors)
X901.2 GasvalvePV(pilotvalve)
X901.4
GasvalveV1(mainvalve,
upstream)
X901.3
GasvalveV2(mainvalve,
downstream)
PilotGp2
X402.3 Ignition
X901.1
GasvalveSV(safetyvalve,
usuallyoutdoors)
X901.2 GasvalvePV(pilotvalve)
X901.4
GasvalveV1(mainvalve,
upstream)
X901.3
GasvalveV2(mainvalve,
downstream)
Figure41:FuelTrainSequencesforGas(shadedindicatesenergized)